Smarten MGC 60
60kVA Smarten MGC Micro-grid Converter
Smarten MGC 60 Parameters |
|
|---|---|
| Physical | |
| AC connection | 3P4W+PE, 3P3W+PE, 2P3W+PE(Split-phase) |
| Rated AC voltage | 208/240(Split-phase)/380/400/415/480Vac 45~62.5Hz |
| Operation ambient temperature | -25~+60°C, derating begins at +45°C |
| Storing ambient temperature | -40~70°C |
| Humidity | 0%~100%RH |
| Altitude | <3km, no derating >3km, derating in accordance with IEC 62040-3 |
| Noise | <60dB |
| CEC efficiency | >97.5% |
| Maximum efficiency | >98.5% |
| Safety standards compliance | CE, UL1741, EN62477 |
| Grid connection compliance | EN50549, VDE4105, AS4777 |
| Topology | Non-isolated |
| Overvoltage category | DC: OVC II 4.5kV AC: OVC III 4kV |
| Dimensions (mm) | 440W*650H*173D |
| Weight (kg) | 40kg |
| Mounting | Wall-mounted or Rack-mounted |
| Ingress Protection | IP30 Air duct with special treatment for moisture and salt mist IP65 Core components |
| NEMA rating | NEMA 3R |
| Grid-Connected Mode | |
| AC rated power | 21kW @240V(Split-phase) 31kW @208V 60kW @400V 62kW @415V 72kW @480V |
| AC rated current | 86A |
| Overload capacity | 1.1 × rated power continuously |
| THDI | <2% |
| Power factor | full quadrants,0~1 leading or lagging |
| Standalone Mode | |
| AC rated power | 21kW @240V(Split-phase) 31kW @208V 60kW @400V 62kW @415V 72kW @480V |
| Overload capacity | 1.1 × rated power continuously 1.25 × rated power for 30s 1.5 × rated power for 3s |
| Power factor | full quadrants,0~1 leading or lagging |
| THDU | <3% for linear loads <5% for non-linear loads (tested with RCD load) |
| Battery Interface Parameters | |
| Battery voltage range | 150V ~ 850V |
| Full load voltage range | 210V ~ 850V |
| Maximum current | 220A |
| Rated charging and discharging power | 60kW |
| Maximum charging and discharging power | Charging 120kW (>410Vdc) Discharging 68kW |
| DC link Parameters | |
| Voltage range | 600V ~ 870V |
| Rated voltage | 720V |
| Maximum input power | 120kW |
| Maximum current | 200A |
| Communication | |
| Parallel Operation | Maximum 32 units, via HS485 |
| Communication interface | HS485, RS485, CAN, Ethernet External AC current analog input External AC voltage analog input Dry contact DO, Dry contact DI |
“